        Ductwork Support Spacing         Tech Brief 13-01 
         
        Question…..can we use 14 foot support spacing for round spiral ductwork? 
         
         
        Overview: 
        SMACNA HVAC Duct Construction Metal and Flexible (2005) Table 5-2 allows for a 
        maximum spacing of 12 feet. In addition SMACNA (2005) stipulates the required wire size, rod, 
        or strap required for proper support. The standard gauges also required by SMACNA (2005) are 
        also required; this is standard practice for Lindab. 
         
        SMACNA (2005) also directs you to utilize SMACNA Round Industrial Duct Construction 
        Standards (RIDCS) for longer spans. 
         
        SMACNA RIDCS 1st edition (1977) has convenient tables for the material gauges for increased 
        spans. In addition, a variety of options are offered for the ductwork support which are more 
        stringent than the SMACNA (2005) requirements. In general, the current SMACNA (2005) 
        gauges are suitable for spans up to 30 feet; however, the more stringent ductwork support 
        guidelines must be followed. 
         
        The current version for SMACNA RIDCS is the 2nd edition (1999) which made a decision 
        (outlined in section 5.3.1) to require 22 gauge minimum. Using this document as the basis of 
        design would then require increase gauges for all ductwork less than 44 inch diameter. This is in 
        addition to the more stringent support detailed in chapter 13 Hanger & Supports. 
         
        1 | Page 
         
         
The words contained in this file might help you see if this file matches what you are looking for:

...Ductwork support spacing tech brief question can we use foot for round spiral overview smacna hvac duct construction metal and flexible table allows a maximum of feet in addition stipulates the required wire size rod or strap proper standard gauges also by are this is practice lindab directs you to utilize industrial standards ridcs longer spans st edition has convenient tables material increased variety options offered which more stringent than requirements general current suitable up however guidelines must be followed version nd made decision outlined section require gauge minimum using document as basis design would then increase all less inch diameter detailed chapter hanger supports page...