 Power Flow Studies
    ◮ Power flow studies are of great importance in planning and
     operation.
    ◮ A power flow study gives the magnitude and angle of the
     voltage at each bus.
    ◮ Once the bus voltage magnitudes and angles are known, the
     real and reactive power flow through each line can be
     computed and hence losses in a system.
    ◮ Power flow studies are a steady state analysis of a power
     system. They are called as load flow studies.
    ◮ Since the loads are specified in terms of power, the resulting
     equations are non-linear algebraic which need to be solved
     iteratively.
    ◮ We use numerical methods such as Gauss-Seidal and
     Newton-Raphson Methods for solving them.
          Power Flow Problem:
          Let Vi be the voltage at ith bus.
                                                   Vi = |Vi| δ
                                                                     i
          Let Yii and Yij be
                                      Y =|Y | θ                Y =|Y | θ
                                        ii        ii    ii       ij        ij     ij
                                                                                      i
          The net current injected into the network at bus ❖ is
                                                                                   N
                         I  =Y V1+Y V2+···+Y V =XY Vn
                          i       i1           i2                    iN    N              in
                                                                                  n=1
          where N be the total number of buses in the network. Let P and
                                                                                                     i
          Qi be the net real and reactive power entering the network at the
                  i
          bus ❖.
                                                P +Q =VI∗
                                                   i        i       i  i
                                                P −Q =V∗I
                                                   i        i       i   i
                                N
                    P −Q =V∗XY Vn
                     i    i   i    in
                               n=1
     On substitution,
                             N
              P −Q =|V| −δ X|Y ||Vn| θ +δ
               i    i   i   i    in    in  n
                             n=1
                       N
              P −Q =X|Y ||V||V | θ +δ −δ
               i    i      in i  n  in  n  i
                       n=1
     Equating real and and imaginary parts,
                   N
              P =X|Y ||V||V |cos(θ +δ −δ )
               i      in  i n    in  n   i
                  n=1
                   N
             Q =−X|Y ||V||V |sin(θ +δ −δ)
              i        in i n    in  n   i
                  n=1
         The above equations are power flow equations in the polar form.
         They are non linear functions of |V| and δ.
                                            P =f (|V|,δ)
                                                     1
                                            Q=f (|V|,δ)
                                                     2
                                                                     i
                                                                   ❖
                                      →P              →P
                                            gi               i,sch              }P,Q
                                      →Q              →Q                            i    i
                                             gi              i,sch
                                                     P ,Q
                                                       di    di
The words contained in this file might help you see if this file matches what you are looking for:

...Power flow studies ow are of great importance in planning and operation a study gives the magnitude angle voltage at each bus once magnitudes angles known real reactive through line can be computed hence losses system steady state analysis they called as load since loads specied terms resulting equations non linear algebraic which need to solved iteratively we use numerical methods such gauss seidal newton raphson for solving them problem let vi ith i yii yij y ii ij net current injected into network is n v xy vn where total number buses p qi entering q on substitution x equating imaginary parts cos sin above polar form functions f gi sch di...