126x Filetype PDF File size 0.32 MB Source: www.iitp.ac.in
Power Flow Studies ◮ Power flow studies are of great importance in planning and operation. ◮ A power flow study gives the magnitude and angle of the voltage at each bus. ◮ Once the bus voltage magnitudes and angles are known, the real and reactive power flow through each line can be computed and hence losses in a system. ◮ Power flow studies are a steady state analysis of a power system. They are called as load flow studies. ◮ Since the loads are specified in terms of power, the resulting equations are non-linear algebraic which need to be solved iteratively. ◮ We use numerical methods such as Gauss-Seidal and Newton-Raphson Methods for solving them. Power Flow Problem: Let Vi be the voltage at ith bus. Vi = |Vi| δ i Let Yii and Yij be Y =|Y | θ Y =|Y | θ ii ii ii ij ij ij i The net current injected into the network at bus ❖ is N I =Y V1+Y V2+···+Y V =XY Vn i i1 i2 iN N in n=1 where N be the total number of buses in the network. Let P and i Qi be the net real and reactive power entering the network at the i bus ❖. P +Q =VI∗ i i i i P −Q =V∗I i i i i N P −Q =V∗XY Vn i i i in n=1 On substitution, N P −Q =|V| −δ X|Y ||Vn| θ +δ i i i i in in n n=1 N P −Q =X|Y ||V||V | θ +δ −δ i i in i n in n i n=1 Equating real and and imaginary parts, N P =X|Y ||V||V |cos(θ +δ −δ ) i in i n in n i n=1 N Q =−X|Y ||V||V |sin(θ +δ −δ) i in i n in n i n=1 The above equations are power flow equations in the polar form. They are non linear functions of |V| and δ. P =f (|V|,δ) 1 Q=f (|V|,δ) 2 i ❖ →P →P gi i,sch }P,Q →Q →Q i i gi i,sch P ,Q di di